GT-WSP-Fp2.00 Outdoor Intumescent Fireproof Coating for Steel Structure

Outdoor Intumescent Fireproof Coating for Steel Structure – Waterborne intumescent coating for outdoor steel fire protection.

  • 2 h rating: ≥3.2 mm; 4.5 kg/m² theoretical consumption.

  • Air spray 0.6–0.8 MPa; nozzle Φ4.0–6.0 mm.

  • Bond strength test result: 0.77 MPa.

Facebook
Twitter
LinkedIn

GT-WSP-Fp2.00 Outdoor Intumescent Fireproof Coating for Steel Structure Description

Overview
Waterborne fireproof coating for steel structures based on special waterborne elastic resin emulsion, flame retardants, blowing agent, and additives.
When exposed to fire, the coating intumesces to form a carbonized fire-resistant thermal insulation layer to delay steel heating and improve fire resistance time.
The document states the product performance meets or exceeds GB 14907-2018 (Steel Structure Fireproof Coatings).

Composition
Special waterborne elastic resin emulsion, high-efficiency flame retardant, blowing agent, and additives (waterborne system).

Typical uses

  • Fire protection for steel structures and building steel space frames (document describes broad application; product name specifies outdoor use).

Technical data (typical)

  • Color: Gray.

  • Gloss: Matt (no gloss).

  • Density / specific gravity: 1.24 kg/L.

  • Shelf life: 12 months.

  • Packaging: 20 kg/pail or 50 kg/pail.

  • Coating theoretical (fire resistance requirement → thickness → theoretical consumption): 2 h → ≥3.2 mm → 4.5 kg/m²; 1.5 h → ≥2.6 mm → 3.2 kg/m²; 1 h → ≥1.7 mm → 2.2 kg/m².

  • Key test results (as listed): bond strength 0.77 MPa; heat resistance 720 h attenuation 7%; damp heat 504 h attenuation 6%; freeze-thaw 15 cycles attenuation 2%; acid resistance 360 h attenuation 4%; alkali resistance 360 h attenuation 2%; salt spray (30 cycles) attenuation 5%; UV radiation (60 cycles) attenuation 4%; fire test: thickness 3.2 mm, steel beam span 5400 mm, 120 min test time, max deflection 28.44 mm, average temperature 518.96°C.

Application data (25°C)

  • Mixing: Single-pack.

  • Induction time: None.

  • Pot life: Unlimited (as stated).

  • Application methods: Air spray, roller (brush also listed under application mode table).

  • Thinner: Water.

  • Maximum dilution: 5% (air spray); 5% (roller).

  • Air spray nozzle diameter: 4.0–6.0 mm.

  • Air spray pressure: 0.6–0.8 MPa.

  • Application notes (thickness control): first coat ≤0.5 mm; subsequent coats ≤0.8 mm; interval between coats not less than 24 h.

  • Coating conditioning for testing (as stated): physico-chemical performance testing conditioning 30 days at 5–35°C; fire performance testing conditioning 50 days at 5–35°C.

Surface preparation

  • Prior to blasting: grind welds, welding spatter, burrs, and chamfer sharp edges.

  • Blast cleaning to Sa 2.5 or power-tool cleaning to St 3; steel must be bare and free of mill scale/oxide scale.

  • Apply coating within 5 h after surface preparation (as stated).

  • Apply at least two coats of anti-corrosion primer first; apply fireproof coating after the anti-corrosion primer is dry.

System compatibility / packing / storage

  • After achieving thickness and hard dry, a dedicated topcoat (tintable) may be applied for protection and decoration; the fireproof coating itself is stated as not tintable.

  • Storage: sealed storage in a ventilated, dry place without direct sunlight; storage temperature 5–35°C (as stated).

  • Shelf life: 12 months.

Contact Us

We would love to speak with you.
Feel free to reach out using the below details.

HUILI fireproof coatings metal paint pail

Indoor Non-Intumescent Fireproof Coating for Steel Structure – Indoor cementitious thermal-insulation fireproof coating for steel.

  • 3 h rating: ≥33 mm; 20–22 kg/m²; 5–6 coats.

  • Air spray 0.6–0.8 MPa; nozzle Φ4.0–6.0 mm.

  • Fire test: 32 mm thickness; 5400 mm span; 3.00 h.

HUILI fireproof coatings metal paint pail

Outdoor Non-Intumescent Fireproof Coating for Steel Structure – Outdoor non-intumescent fireproof coating for steel structures.

  • 3 h rating: ≥33 mm; 20–22 kg/m²; 5–6 coats.

  • Bond strength test result: 0.11 MPa.

  • Fire test: 33 mm thickness; 5400 mm span; 3.00 h.

HUILI anti-corrosion coatings metal paint pail

Inorganic Zinc Silicate Primer (2K) – Two-component inorganic zinc silicate primer for long-term steel corrosion protection with cathodic protection.

  • For blast-cleaned steel; surface preparation Sa 3 (not lower than Sa 2.5) is specified.

  • Fast drying at 25°C, RH 70–85%: touch dry 10 min; hard dry 2 h; cured 24 h.

  • Mix ratio 28:7; thinner X-11 inorganic zinc thinner (5–20%); compatible with epoxy/PU coating systems.

HUILI anti-corrosion coatings metal paint pail

Epoxy Red Lead Anti-Rust Primer (2K) – Two-component epoxy anti-rust primer for steel corrosion protection.

  • For tanks, gas holders, offshore/underwater steel structures, and buried pipelines.
  • Mix ratio 28:4; pot life 4 h (25°C).
  • Recoat 24 h–7 d (25°C); overcoatable with epoxy and polyurethane systems.

INQUIRY NOW