Cementitious hydrocarbon fire-resistant coating engineered for petrochemical and oil refining facilities exposed to hydrocarbon flame. Impact-resistant and crack-resistant with outstanding weathering performance. Sa2.5 prep, 24–33mm total application thickness.
Overview
Special outdoor non-intumescent fireproof coating designed for hydrocarbon flames, forming a fire-resistant thermal insulation protective layer on outdoor steel structures.
The document states it does not corrode steel, does not chemically react with anti-corrosion primers, has no irritating odor, produces no smoke during fire exposure, and does not release harmful gases.
The document states the product performance meets or exceeds GB 14907-2018 (Steel Structure Fireproof Coatings).
Composition
Lightweight thermal insulation materials, refractory cement, and refractory flame-retardant materials (composite).
Typical uses
Fire protection of outdoor steel structures in petrochemical refining and chemical enterprises where hydrocarbon flame resistance is required.
Technical data (typical)
Color: Gray.
Gloss: Matt (no gloss).
Density / specific gravity: 0.4 kg/L.
Shelf life: 12 months (shown in the physical data table).
Packaging: 20 kg/bag.
Coating theoretical (fire resistance requirement → thickness → number of coats → theoretical consumption): 3 h → ≥33 mm → 5–6 coats → 20–22 kg/m²; 2 h → ≥24 mm → 3–4 coats → 15–17 kg/m²; 1 h → ≥16 mm → 2–3 coats → 10–12 kg/m².
Key test results (as listed): bond strength 0.11 (MPa shown in the standard requirement column); heat resistance 720 h attenuation 8%; damp heat 504 h attenuation 7%; freeze-thaw 15 cycles attenuation 2%; acid resistance 360 h attenuation 6%; alkali resistance 360 h attenuation 1%; salt spray (30 cycles) attenuation 5%; UV radiation (60 cycles) attenuation 6%; fire test: measured thickness 33 mm, steel beam span 5400 mm, test time 3.00 h, max deflection 29.59 mm, average temperature 521.31°C.
Application data (25°C)
Thinner: Water.
Application methods: Air spray and trowel application are stated.
Spray equipment (as listed): continuous air supply pressure 0.6–0.8 MPa; spray gun nozzle diameter Φ4.0–6.0 mm.
Wet mix usable time (as stated): wet material must be used within 2 h (given in the interface layer / trowel mixing notes).
Trowel application control (as stated): each pass thickness 6–8 mm; interval about 24 h between passes.
Mixing ratio: coating : water : binder is referenced for spray and trowel application (numeric values are not shown in the provided table cells).
Surface preparation
Prior to blasting: grind welds, remove welding spatter and burrs, and round sharp edges.
Blast cleaning to Sa 2.5, or power-tool cleaning to St 3 to ensure steel is fully exposed and free of mill scale/oxide scale.
Apply coating within 5 h after surface preparation (as stated).
Apply at least two coats of anti-corrosion primer first; apply the fireproof coating after the anti-corrosion primer is dry.
System compatibility / packing / storage
The document states no chemical reaction with anti-corrosion primers.
After the coating is thoroughly dry, two coats of decorative topcoat (tintable) may be applied to improve service life and appearance (as stated).
Storage: sealed, stored off the ground in a ventilated and dry place without direct sunlight; prevent moisture and rain ingress; storage temperature 5–35°C.
Shelf life: 9 months (stated in the storage section).
Packaging: 20 kg/bag.
We would love to speak with you.
Feel free to reach out using the below details.
2K epoxy sealer primer engineered for deep penetration and encapsulation of concrete and cement substrates. Seals and stabilizes surfaces to optimize adhesion for subsequent coating systems. Surface dry in 1 hour, full cure in 7 days.
Industrial anti-corrosion and protective coating manufacturer. Direct supply from factory — no agents. ISO 9001 certified. Exporting to 30+ countries.