GT-NSP-Fp2.00 Indoor Intumescent Fireproof Coating for Steel Structure

Indoor Intumescent Fireproof Coating for Steel Structure – Waterborne intumescent coating for indoor steel fire protection.

  • 2 h rating: ≥3.3 mm; 4.6 kg/m² theoretical consumption.

  • Water-thinnable; max dilution 5%.

  • Bond strength test result: 0.82 MPa.

GT-NSP-Fp2.00 Indoor Intumescent Fireproof Coating for Steel Structure Descriotion

Overview
Waterborne fireproof coating for steel structures based on special waterborne elastic resin emulsion, flame retardants, blowing agent, and functional additives.
When exposed to fire, the coating intumesces and forms a carbonized fire-resistant thermal insulation layer to delay steel temperature rise and improve fire resistance time.
The document states the product performance meets or exceeds GB 14907-2018 (Steel Structure Fireproof Coatings).

Composition
Special waterborne elastic resin emulsion, high-efficiency flame retardant, blowing agent, and functional additives (waterborne system).

Typical uses

  • Fire protection for indoor steel structures and building steel space frames (grid structures).

Technical data (typical)

  • Color: Gray.

  • Gloss: Matt (no gloss).

  • Density / specific gravity: 1.24 kg/L.

  • Shelf life: 12 months.

  • Packaging: 20 kg/pail or 50 kg/pail.

  • Coating theoretical (fire resistance requirement → DFT → theoretical consumption): 2 h → ≥3.3 mm → 4.6 kg/m²; 1.5 h → ≥2.6 mm → 3.2 kg/m²; 1 h → ≥1.7 mm → 2.2 kg/m².

  • Key test results (as listed): initial drying crack resistance: no cracks; bond strength: 0.82 MPa; heat/cold cycling (15 cycles): no cracking/flaking/blistering, insulation efficiency attenuation 4%; water resistance (24 h): no delamination/blistering/peeling, insulation efficiency attenuation 9%; fire test: measured thickness 3.3 mm, steel beam span 5400 mm, test time 123 min (124 min stated during test), max deflection 41.52 mm, average temperature 539.96°C.

Application data (25°C)

  • Mixing: Single-pack.

  • Induction time: None.

  • Pot life: Unlimited (as stated).

  • Application methods: Air spray, roller (brush also listed under application mode table).

  • Thinner: Water.

  • Maximum dilution: 5% (air spray); 5% (roller/brush).

  • Air spray nozzle diameter: 4.0–6.0 mm.

  • Air spray pressure: 0.6–0.8 MPa.

  • Application notes (thickness control): first coat ≤0.5 mm; subsequent coats ≤0.8 mm; interval between coats ≥24 h.

  • Curing/conditioning for testing (as stated): physico-chemical performance testing conditioning 30 days at 5–35°C; fire performance testing conditioning 50 days at 5–35°C.

Surface preparation

  • Prior to blasting: grind welds, welding spatter, burrs, and chamfer sharp edges.

  • Blast cleaning to Sa 2.5 or power-tool cleaning to St 3; steel surface must be bare and free of mill scale/oxide scale.

  • Apply coating within 5 h after surface preparation (as stated).

  • Apply at least two coats of anti-corrosion primer first; apply fireproof coating after the anti-corrosion primer is dry.

System compatibility / packing / storage

  • Optional dedicated topcoat (tintable) can be applied for protection and decoration after the fireproof coating reaches thickness and is hard dry; the fireproof coating itself is stated as not tintable.

  • Storage: sealed storage in a ventilated, dry place without direct sunlight; storage temperature 5–35°C (as stated).

  • Shelf life: 12 months.

Related Products

HUILI anti-rust coatings metal paint pail

CSPE cooling tower damp-proof coating for inner wall anti-corrosion service.

  • For cooling tower inner wall protection.

  • Single-component; min recoat 12 h at 25°C.

  • Resists freeze-thaw, damp heat, and mildew.

HUILI anti-rust coatings metal paint pail

Polyurethane cooling tower damp-proof coating (2K) for waterproof anti-corrosion lining.

  • For cooling towers, sewage tanks, mines, underground buildings.

  • Primer ratio 24:3; topcoat ratio 18:3.

  • Pot life 4 h; min recoat 12 h.

HUILI anti-rust coatings metal paint pail

Premium polyurethane marking coating (2K) for steel structures and concrete chimneys.

  • For chimney marking and protection.

  • Mixing ratio 18:3; pot life 4 h.

  • High gloss; fully hardened 7 d at 25°C.

HUILI anti-rust coatings metal paint pail

Epoxy bitumen cooling tower damp-proof coating (2K) for cooling tower inner wall protection.

  • For cooling towers, sewage tanks, underground mines.

  • Mixing ratio 25:2.5; pot life 4 h.

  • Waterproof, anti-seepage, and mildew resistant.

Contact Us

We would love to speak with you.
Feel free to reach out using the below details.