GT-NSF-Fp3.00 Indoor Non-Intumescent Fireproof Coating for Steel Structure

Indoor Non-Intumescent Fireproof Coating for Steel Structure – Indoor cementitious thermal-insulation fireproof coating for steel.

  • 3 h rating: ≥33 mm; 20–22 kg/m²; 5–6 coats.

  • Air spray 0.6–0.8 MPa; nozzle Φ4.0–6.0 mm.

  • Fire test: 32 mm thickness; 5400 mm span; 3.00 h.

GT-NSF-Fp3.00 Indoor Non-Intumescent Fireproof Coating for Steel Structure Descriotion

Overview
Indoor non-intumescent fireproof coating for steel structures, formulated to form a fire-resistant thermal insulation protective layer and reduce fire damage to load-bearing steel structures.
The document states it does not corrode steel, does not chemically react with anti-corrosion primers, has no irritating odor, produces no smoke during fire exposure, and does not release harmful gases.
The document states the product performance meets or exceeds GB 14907-2018 (Steel Structure Fireproof Coatings).

Composition
Lightweight thermal insulation materials, refractory cement, and inorganic hydraulic materials.

Typical uses

  • The document lists stations, docks, warehouses, stadiums, exhibition centers, and office buildings (application text in the file).

Technical data (typical)

  • Color: Gray.

  • Gloss: Matt (no gloss).

  • Density / specific gravity: 0.4 kg/L.

  • Shelf life: 12 months (shown in the physical data table).

  • Packaging: 20 kg/bag.

  • Coating theoretical (fire resistance requirement → thickness → number of coats → theoretical consumption): 3 h → ≥33 mm → 5–6 coats → 20–22 kg/m²; 2 h → ≥24 mm → 3–4 coats → 15–17 kg/m²; 1 h → ≥16 mm → 2–3 coats → 10–12 kg/m².

  • Key test results (as listed): bond strength 0.11 (MPa not explicitly shown in the result cell); heat/cold cycling (15 cycles) insulation efficiency attenuation 3%; fire test: measured thickness 32 mm, steel beam span 5400 mm, test time 3.00 h, max deflection 29.80 mm, average temperature 523.98°C.

Application data (25°C)

  • Thinner: Water.

  • Application methods: Air spray and trowel application are stated.

  • Spray equipment (as listed): continuous air supply pressure 0.6–0.8 MPa; spray gun nozzle diameter Φ4.0–6.0 mm.

  • Mixing ratio: coating : water : binder is referenced for spray and trowel application (numeric values are not shown in the provided table cells).

  • Wet mix usable time (as stated): wet material must be used within 2 h (given in the interface layer / trowel mixing notes).

  • Trowel application control (as stated): each pass thickness 6–8 mm; interval about 24 h between passes; keep the surface rough between layers to improve bonding.

  • Curing/conditioning (as stated): after reaching design thickness and final set, keep moist curing for 7 days (water spray suggested); for fire performance testing, natural curing ≥35 days at 5–35°C.

Surface preparation

  • Prior to blasting: grind welds, remove welding spatter and burrs, and round sharp edges.

  • Blast cleaning to Sa 2.5, or power-tool cleaning to St 3 to ensure steel is fully exposed and free of mill scale/oxide scale.

  • Apply coating within 5 h after surface preparation (as stated).

  • Apply at least two coats of anti-corrosion primer first; apply the fireproof coating after the anti-corrosion primer is dry.

System compatibility / packing / storage

  • The document states no chemical reaction with anti-corrosion primers.

  • After the coating is thoroughly dry, two coats of decorative topcoat (tintable) may be applied to improve service life and appearance (as stated).

  • Storage: sealed, stored off the ground in a ventilated and dry place without direct sunlight; prevent moisture and rain ingress; storage temperature 5–35°C.

  • Shelf life: 9 months (stated in the storage section).

  • Packaging: 20 kg/bag.

Contact Us

We would love to speak with you.
Feel free to reach out using the below details.

HUILI specialty coatings metal paint pail

High-Grade Epoxy Enamel (2K) – Epoxy enamel for decorative heavy-duty corrosion protection.

  • For steel structures and concrete surfaces.

  • Mix ratio 20:4; pot life 4 h.

  • Recoat 12 h–7 d; X-7 thinner 2–8%.

HUILI anti-corrosion coatings metal paint pail

Inorganic Zinc-Rich Primer (2K) – Two-component ethyl silicate zinc-rich primer for cathodic protection of blast-cleaned steel.

  • General-purpose use for bridges, towers, gas holders, oil tanks, oil/gas pipelines, and industrial steel structures.

  • High zinc dust content with stated water/oil/media resistance and welding/cutting resistance.

  • Sa 3 surface preparation (not lower than Sa 2.5); touch dry 10 min at 25°C, RH 70–85%.

HUILI anti-corrosion coatings metal paint pail

Special Epoxy Primer (2K) – Two-component special epoxy primer for industrial corrosion protection.

  • For power, bridge, petrochemical, marine, and port facilities/equipment.

  • Pot life 2 h (25°C); mix ratio 25:2.5.

  • Compatible with epoxy MIO intermediate and epoxy/PU topcoat systems.

HUILI anti-corrosion coatings metal paint pail

Epoxy Zinc Primer (2K, C6-Modified) – Two-component epoxy zinc primer (C6-modified) for cathodic-protection priming.

  • Salt spray resistance 1300 h (as stated).

  • Theoretical consumption 0.25 kg/m² at 50 µm DFT (losses not included).

  • For offshore platforms, underwater steel, pipelines, oil tanks, bridges, and petrochemical steel structures.

INQUIRY NOW

Contact Information